Where can I confirm this?
Reports and contact
- City of Orem Water Quality Report 2026Report year: 2026Open report ↗
Provider phone: 801-229-7530
Utah · Public water system UTAH25020
Review this provider’s public water records. Confirm the name and provider ID on your bill before applying these results to your home.
Plain-language summary
OREM CITY WATER SYSTEM is listed as a community water system in Utah County. The newest annual report year listed here is 2026. This page includes 264 provider-specific measurement records; use the stated year and units when reading each result.
Available measurements include Total Coliform, E. coli, Turbidity, Total Organic Carbon. Their report and sample years appear with each result.
Public-system records do not describe every faucet. Your home’s plumbing can affect water at the tap, and regulatory records may lag local notices.
What do the available sources measure?
A detection is not automatically a violation. Compare the original value and unit with the applicable standard and the report’s compliance text.
Lists detected contaminants from 2021–2025 and separate City of Orem and DACRWTP results.
| Contaminant or characteristic | Sample period | Reported result or range | Unit | Limit supplied by source | Source compliance statement |
|---|---|---|---|---|---|
| Total ColiformMicrobiological | 2025 | 0–0Separate regional source: 0–0 % positive per month. See the original report for the source name and context. | % positive per month | 5% | The source report did not identify this measurement as a violation. |
| E. coliMicrobiological | 2025 | 0–0Separate regional source: 0–0 % positive per month. See the original report for the source name and context. | % positive per month | TT | The source report did not identify this measurement as a violation. |
| TurbidityPhysical | 2023, 2024, 2025 | 0–0.32Separate regional source: 0.013–0.044 NTU. See the original report for the source name and context. | NTU | 95% <0.3 | The source report did not identify this measurement as a violation. |
| Total Organic CarbonOrganic Material | 2024 | MNR–0Separate regional source: 1.59–2.97 mg/L. See the original report for the source name and context. | mg/L | TT | The source report did not identify this measurement as a violation. |
| UV-254Organic Material | 2024 | MNR–0Separate regional source: 0.011–0.042 1/cm. See the original report for the source name and context. | 1/cm | Unregulated | The source report did not identify this measurement as a violation. |
| ChlorineDisinfectants | 2024 | 0.05–1.3Separate regional source: 0.58–2.08 mg/L. See the original report for the source name and context. | mg/L | 4 | The source report did not identify this measurement as a violation. |
| Total Trihalomethanes (TTHM)Disinfection Byproducts | 2025 | 0–54.78Separate regional source: 11.0–54.0 µg/L. See the original report for the source name and context. | µg/L | 80 | The source report did not identify this measurement as a violation. |
| Haloacetic Acids (HAA5)Disinfection Byproducts | 2025 | 0–32.612Separate regional source: 6.0–42.0 µg/L. See the original report for the source name and context. | µg/L | 60 | The source report did not identify this measurement as a violation. |
| ChloroformVolatile Organic Compounds | 2025 | 0–44.4Separate regional source: 7.0–41.0 µg/L. See the original report for the source name and context. | µg/L | None established | The source report did not identify this measurement as a violation. |
| BromodichloromethaneVolatile Organic Compounds | 2025 | 0–8.5Separate regional source: 2.6–12.0 µg/L. See the original report for the source name and context. | µg/L | None established | The source report did not identify this measurement as a violation. |
| DibromochloromethaneVolatile Organic Compounds | 2025 | 0–2.6Separate regional source: 1.0–4.8 µg/L. See the original report for the source name and context. | µg/L | 80 | The source report did not identify this measurement as a violation. |
| AntimonyInorganic | 2021, 2023, 2024, 2025 | 0–0Separate regional source: 0.007–0.007 µg/L. See the original report for the source name and context. | µg/L | 6 | The source report did not identify this measurement as a violation. |
| ArsenicInorganic | 2021, 2023, 2024, 2025 | 0–1.9Separate regional source: 0–0 µg/L. See the original report for the source name and context. | µg/L | 10 | The source report did not identify this measurement as a violation. |
| BariumInorganic | 2021, 2023, 2024, 2025 | 0.03–0.087Separate regional source: 0.063–0.063 mg/L. See the original report for the source name and context. | mg/L | 2 | The source report did not identify this measurement as a violation. |
| CopperInorganic | 2024 | 0.025–0.559Separate regional source: ND–ND mg/L. See the original report for the source name and context. | mg/L | 1.3 | The source report did not identify this measurement as a violation. |
| LeadInorganic | 2024 | 0–0.0068Separate regional source: ND–ND mg/L. See the original report for the source name and context. | mg/L | 0.010 | The source report did not identify this measurement as a violation. |
| FluorideInorganic | 2021, 2023, 2024 | 0–0.205Separate regional source: 0.117–0.117 mg/L. See the original report for the source name and context. | mg/L | 4 | The source report did not identify this measurement as a violation. |
| NitrateInorganic | 2025 | 0.356–1.827Separate regional source: 0.22–0.22 mg/L. See the original report for the source name and context. | mg/L | 10 | The source report did not identify this measurement as a violation. |
| SeleniumInorganic | 2021, 2023, 2024, 2025 | 0–4.2Separate regional source: 0–0 µg/L. See the original report for the source name and context. | µg/L | 50 | The source report did not identify this measurement as a violation. |
| Gross alphaRadioactive | 2019, 2022, 2023, 2024 | -0.4–4.1Separate regional source: 0.5–0.5 pCi/L. See the original report for the source name and context. | pCi/L | 15 | The source report did not identify this measurement as a violation. |
| Radium 228Radioactive | 2019, 2022, 2023, 2024 | 0.08–0.906Separate regional source: 0.28–0.28 pCi/L. See the original report for the source name and context. | pCi/L | 5 | The source report did not identify this measurement as a violation. |
| All other PFAS parametersPFAS | 2020, 2021, 2025 | ND–NDSeparate regional source: ND–ND µg/L. See the original report for the source name and context. | µg/L | Varies | The source report did not identify this measurement as a violation. |
| LithiumUCMR 5 | 2025 | 0–26.9 | µg/L | Unregulated | The source report did not identify this measurement as a violation. |
| Polyfluoroalkyl substancesUCMR 5 | 2025 | ND–ND | µg/L | Varies | The source report did not identify this measurement as a violation. |
| Perfluoroalkyl substancesUCMR 5 | 2025 | ND–ND | µg/L | Varies | The source report did not identify this measurement as a violation. |
| All other parametersPesticides, PCBs, VOCs | 2023, 2024, 2025 | ND–NDSeparate regional source: ND–ND µg/L. See the original report for the source name and context. | µg/L | Varies | The source report did not identify this measurement as a violation. |
| Copper (tap)Lead and Copper Rule | 2024 | 0.237 (90th percentile); 0 sites over AL | mg/L | AL 1.3 | The source report did not identify this measurement as a violation. |
| Lead (tap)Lead and Copper Rule | 2024 | 0.0022 (90th percentile); 0 sites over AL | mg/L | AL 0.010 | The source report did not identify this measurement as a violation. |
| AlkalinitySecondary Standard | 2018–2025 | MNR–MNRSeparate regional source: 112–144 mg/L. See the original report for the source name and context. | mg/L | None established | The source report did not identify this measurement as a violation. |
| CalciumSecondary Standard | 2021 | 39.4–61.9Separate regional source: MNR–MNR mg/L. See the original report for the source name and context. | mg/L | None established | The source report did not identify this measurement as a violation. |
| ChlorideSecondary Standard | 2021 | 0.711–46.9Separate regional source: MNR–MNR mg/L. See the original report for the source name and context. | mg/L | 250 | The source report did not identify this measurement as a violation. |
| ColorSecondary Standard | 2018–2025 | 1–1Separate regional source: ND–3.0 Pt-Co. See the original report for the source name and context. | Pt-Co | 15 | The source report did not identify this measurement as a violation. |
| ConductanceSecondary Standard | 2018–2025 | 203–708Separate regional source: 371–481 µmhos/cm. See the original report for the source name and context. | µmhos/cm | None established | The source report did not identify this measurement as a violation. |
| Corrosivity — LangelierSecondary Standard | 2021–2023 | -0.301–0.458Separate regional source: MNR–MNR SI. See the original report for the source name and context. | SI | -0.3 to 0.3 | The source report did not identify this measurement as a violation. |
| HardnessSecondary Standard | 2018–2025 | 120–428Report also gives 7–25 grains/gallon for Orem and 6.55–9 grains/gallon for DACRWTP.Separate regional source: 112–154 mg/L. See the original report for the source name and context. | mg/L | None established | The source report did not identify this measurement as a violation. |
| IronSecondary Standard | 2018, 2021 | 0–0Separate regional source: ND–21.6 µg/L. See the original report for the source name and context. | µg/L | None established | The source report did not identify this measurement as a violation. |
| ManganeseSecondary Standard | 2021 | 0–0.0373Separate regional source: MNR–MNR mg/L. See the original report for the source name and context. | mg/L | 0.05 | The source report did not identify this measurement as a violation. |
| OdorSecondary Standard | 2021 | 1–1Separate regional source: MNR–MNR TON. See the original report for the source name and context. | TON | 3 | The source report did not identify this measurement as a violation. |
| pHSecondary Standard | 2018–2025 | 7.21–8.28Separate regional source: 7.60–7.98 pH. See the original report for the source name and context. | pH | 6.5–8.5 | The source report did not identify this measurement as a violation. |
| SodiumSecondary Standard | 2021, 2023, 2024, 2025 | 0–35.531Separate regional source: 7.6–58 mg/L. See the original report for the source name and context. | mg/L | 500 | The source report did not identify this measurement as a violation. |
| SulfateSecondary Standard | 2021, 2023, 2024, 2025 | 8.78–63.004Separate regional source: 40.4–40.4 mg/L. See the original report for the source name and context. | mg/L | 250 | The source report did not identify this measurement as a violation. |
| Total Dissolved SolidsSecondary Standard | 2021, 2023, 2024, 2025 | 112–388Separate regional source: 249–328 mg/L. See the original report for the source name and context. | mg/L | 500 | The source report did not identify this measurement as a violation. |
| ZincSecondary Standard | 2021 | 0–0.00613Separate regional source: MNR–MNR mg/L. See the original report for the source name and context. | mg/L | 5 | The source report did not identify this measurement as a violation. |
| Contaminant or characteristic | Sample period | Reported result or range | Unit | Limit supplied by source | Source compliance statement |
|---|---|---|---|---|---|
| 11Cl-PF3OUdSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 4:2 FTSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 6:2 FTSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 8:2 FTSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 9Cl-PF3ONSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| ADONAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| HFPO-DAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NEtFOSAAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NFDHAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.02Reporting limit: 0.02 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NMeFOSAAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.006Reporting limit: 0.006 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDoAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFEESAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMBAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMPAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFNAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeSUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.008Reporting limit: 0.008 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTrDAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.007Reporting limit: 0.007 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFUnAUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| lithiumUCMR 5 monitoringWell #7 (1300 E. 600 N. Palisade D.) · Sample Tap (post chlorination)Source stream: 00010/WS010 | 2025Collected: 2025-07-21 | 23.3Reporting limit: 9 µg/LMethod: EPA 200.7Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 11Cl-PF3OUdSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 4:2 FTSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 6:2 FTSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 8:2 FTSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 9Cl-PF3ONSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| ADONAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| HFPO-DAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NEtFOSAAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NFDHAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.02Reporting limit: 0.02 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NMeFOSAAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.006Reporting limit: 0.006 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDoAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFEESAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMBAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMPAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFNAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeSUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.008Reporting limit: 0.008 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTrDAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.007Reporting limit: 0.007 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFUnAUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| lithiumUCMR 5 monitoringWell #9 (900 E 800 S) · Well #9 (900 E 800 S)Source stream: 00012/WS012 | 2025Collected: 2025-07-08 | 21.3Reporting limit: 9 µg/LMethod: EPA 200.7Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 11Cl-PF3OUdSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 4:2 FTSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 6:2 FTSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 8:2 FTSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 9Cl-PF3ONSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| ADONAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| HFPO-DAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NEtFOSAAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NFDHAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.02Reporting limit: 0.02 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NMeFOSAAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.006Reporting limit: 0.006 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDoAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFEESAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMBAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMPAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFNAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeSUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.008Reporting limit: 0.008 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTrDAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.007Reporting limit: 0.007 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFUnAUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| lithiumUCMR 5 monitoringCentral Utah WCD - Utah Valley Intertie · Entry Point to Dist. SystemSource stream: 06586/WS009 | 2025Collected: 2025-10-14 | 12.3Reporting limit: 9 µg/LMethod: EPA 200.7Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 11Cl-PF3OUdSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 4:2 FTSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 6:2 FTSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 8:2 FTSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 9Cl-PF3ONSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| ADONAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| HFPO-DAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NEtFOSAAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NFDHAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.02Reporting limit: 0.02 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NMeFOSAAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.006Reporting limit: 0.006 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDoAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFEESAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMBAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMPAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFNAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeSUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.008Reporting limit: 0.008 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTrDAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.007Reporting limit: 0.007 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFUnAUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| lithiumUCMR 5 monitoringWell #8 (300 E. 700 S, Scera Park) · Sample Tap (post chlorination)Source stream: 90011/WS011 | 2025Collected: 2025-07-21 | 16.5Reporting limit: 9 µg/LMethod: EPA 200.7Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 11Cl-PF3OUdSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 4:2 FTSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 6:2 FTSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 8:2 FTSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 9Cl-PF3ONSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| ADONAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| HFPO-DAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NEtFOSAAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NFDHAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.02Reporting limit: 0.02 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NMeFOSAAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.006Reporting limit: 0.006 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDoAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFEESAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMBAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMPAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFNAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeSUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.008Reporting limit: 0.008 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTrDAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.007Reporting limit: 0.007 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFUnAUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| lithiumUCMR 5 monitoringGrouped Sample Source #1, Alta Spring · Sample Tap (post chlorination)Source stream: 90089/SS089 | 2025Collected: 2025-07-08 | <9Reporting limit: 9 µg/LMethod: EPA 200.7Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 11Cl-PF3OUdSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 4:2 FTSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 6:2 FTSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 8:2 FTSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 9Cl-PF3ONSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| ADONAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| HFPO-DAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NEtFOSAAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NFDHAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.02Reporting limit: 0.02 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NMeFOSAAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.006Reporting limit: 0.006 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDoAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFEESAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMBAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMPAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFNAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeSUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.008Reporting limit: 0.008 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTrDAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.007Reporting limit: 0.007 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFUnAUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| lithiumUCMR 5 monitoringGrouped Source Sample Station 2 · Sample Tap (post chlorination)Source stream: 90185/SS185 | 2025Collected: 2025-07-08 | <9Reporting limit: 9 µg/LMethod: EPA 200.7Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 11Cl-PF3OUdSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 4:2 FTSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 6:2 FTSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 8:2 FTSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| 9Cl-PF3ONSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| ADONAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| HFPO-DAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NEtFOSAAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NFDHAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.02Reporting limit: 0.02 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| NMeFOSAAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.006Reporting limit: 0.006 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.005Reporting limit: 0.005 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFBSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFDoAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFEESAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHpSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFHxSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMBAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFMPAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFNAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFOSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.003Reporting limit: 0.003 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFPeSUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.004Reporting limit: 0.004 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.008Reporting limit: 0.008 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFTrDAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.007Reporting limit: 0.007 µg/LMethod: EPA 537.1Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| PFUnAUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | <0.002Reporting limit: 0.002 µg/LMethod: EPA 533Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
| lithiumUCMR 5 monitoringGrouped Source Sample Station 3 · Sample Tap (post chlorination)Source stream: 90281/SS281 | 2025Collected: 2025-07-08 | 15.7Reporting limit: 9 µg/LMethod: EPA 200.7Individual sample result at the named facility and sample point. A < result is below the UCMR minimum reporting level (MRL), not zero. The MRL is an analytical reporting threshold, not a drinking-water limit. | µg/L | Not supplied | UCMR monitoring results are not a regulatory compliance determination. |
These are 90th-percentile monitoring summaries for the stated reporting periods. Individual sample dates are not supplied. A reported zero is retained as published; it does not establish that lead or copper is absent at an individual faucet.
| Contaminant or characteristic | Sample period | Reported result or range | Unit | Limit supplied by source | Source compliance statement |
|---|---|---|---|---|---|
| Lead (90th percentile)Lead and Copper Rule monitoring · 90th percentileSource stream: monitoring-period/2022-01-01/2024-12-31 | 2022-01-01 to 2024-12-31 (reporting period) | 0.0022System-level 90th percentile of tap samples for the stated monitoring period. The period boundaries are reporting windows, not individual sample dates. A missing result-sign code is retained as unspecified; a zero is not relabeled as a non-detection. Individual household lead or copper concentrations can differ. | mg/L | Not supplied | A monitoring-period 90th percentile is not a compliance determination or a measurement of an individual household's water. |
| Lead (90th percentile)Lead and Copper Rule monitoring · 90th percentileSource stream: monitoring-period/2022-01-01/2024-12-31 | 2022-01-01 to 2024-12-31 (reporting period) | 0.0022System-level 90th percentile of tap samples for the stated monitoring period. The period boundaries are reporting windows, not individual sample dates. A missing result-sign code is retained as unspecified; a zero is not relabeled as a non-detection. Individual household lead or copper concentrations can differ. | mg/L | Not supplied | A monitoring-period 90th percentile is not a compliance determination or a measurement of an individual household's water. |
These are annual monitoring averages, not individual sample results or compliance determinations. A reported zero does not establish that every sample was below detection. Sampling years are shown separately from the date this site retrieved the data.
Historical annual means from Utah public monitoring records. Latest published years vary by contaminant and provider; seasonal and emergency sources are excluded. Sampling frequency and within-system variability differ. These averages cannot establish an individual tap result, detection status, or current compliance.
| Contaminant or characteristic | Sample period | Reported result or range | Unit | Limit supplied by source | Source compliance statement |
|---|---|---|---|---|---|
| Haloacetic Acids Five (HAA5)Historical annual monitoring average · Annual mean | 2023 | 1.00 | µg/L | Not supplied | This annual-mean dataset does not determine compliance. |
| Total Trihalomethanes (TTHM)Historical annual monitoring average · Annual mean | 2023 | 3.44 | µg/L | Not supplied | This annual-mean dataset does not determine compliance. |
| Trichloroethene (TCE)Historical annual monitoring average · Annual mean | 2022 | 0.25 | µg/L | Not supplied | This annual-mean dataset does not determine compliance. |
| Radium-228Historical annual monitoring average · Annual mean | 2022 | 0.53 | pCi/L | Not supplied | This annual-mean dataset does not determine compliance. |
| Tetrachloroethene (PCE)Historical annual monitoring average · Annual mean | 2022 | 0.25 | µg/L | Not supplied | This annual-mean dataset does not determine compliance. |
| NitrateHistorical annual monitoring average · Annual mean | 2023 | 0.40 | mg/L | Not supplied | This annual-mean dataset does not determine compliance. |
| Di (2-Ethylhexyl) Phthalate (DEHP)Historical annual monitoring average · Annual mean | 2022 | 0.65 | µg/L | Not supplied | This annual-mean dataset does not determine compliance. |
| AtrazineHistorical annual monitoring average · Annual mean | 2022 | 0.11 | µg/L | Not supplied | This annual-mean dataset does not determine compliance. |
| ArsenicHistorical annual monitoring average · Annual mean | 2022 | 0.25 | µg/L | Not supplied | This annual-mean dataset does not determine compliance. |
What violation records are reported?
Health-based, treatment, monitoring, and reporting records have different meanings. Resolution status and source dates remain visible.
| Period | Contaminant / rule | Category | Status | Resolution |
|---|---|---|---|---|
| Not available to Not available | Mercury1035 | Monitoring Or Reporting | Archived | Not available |
| Not available to Not available | Barium1010 | Monitoring Or Reporting | Archived | Not available |
| Not available to Not available | Selenium1045 | Monitoring Or Reporting | Archived | Not available |
| Not available to Not available | Nitrate1040 | Monitoring Or Reporting | Archived | Not available |
| Not available to Not available | Cadmium1015 | Monitoring Or Reporting | Archived | Not available |
| Not available to Not available | Arsenic1005 | Monitoring Or Reporting | Archived | Not available |
| Not available to Not available | Fluoride1025 | Monitoring Or Reporting | Archived | Not available |
| Not available to Not available | Chromium1020 | Monitoring Or Reporting | Archived | Not available |
| January 7, 2024 to December 7, 2024 | Consumer Confidence Rule7000 | Monitoring Or Reporting | Resolved | December 7, 2024 |
| January 1, 2020 to Not available | 1,2-Dichloropropane2983 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Tetrachloroethylene2987 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Benzene2990 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Toluene2991 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | 1,2,4-Trichlorobenzene2378 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | cis-1,2-Dichloroethylene2380 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | o-Dichlorobenzene2968 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | p-Dichlorobenzene2969 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Vinyl chloride2976 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | trans-1,2-Dichloroethylene2979 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | 1,2-Dichloroethane2980 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | 1,1,1-Trichloroethane2981 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Carbon tetrachloride2982 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | DICHLOROMETHANE2964 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Ethylbenzene2992 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | 1,1-Dichloroethylene2977 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | CHLOROBENZENE2989 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | 1,1,2-Trichloroethane2985 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Xylenes, Total2955 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Styrene2996 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2020 to Not available | Trichloroethylene2984 | Monitoring Or Reporting | Resolved | Not available |
| January 10, 2014 to Not available | Arsenic1005 | Monitoring Or Reporting | Resolved | Not available |
| January 4, 2013 to Not available | Radium-2284030 | Monitoring Or Reporting | Resolved | Not available |
| January 4, 2013 to Not available | Gross Alpha, Excl. Radon and U4000 | Monitoring Or Reporting | Resolved | Not available |
| January 4, 2013 to Not available | Radium-2264020 | Monitoring Or Reporting | Resolved | Not available |
| January 10, 2012 to February 10, 2012 | Gross Alpha, Excl. Radon and U4000 | Monitoring Or Reporting | Resolved | February 10, 2012 |
| January 10, 2012 to February 10, 2012 | Radium-2264020 | Monitoring Or Reporting | Resolved | February 10, 2012 |
| January 10, 2012 to February 10, 2012 | Radium-2284030 | Monitoring Or Reporting | Resolved | February 10, 2012 |
| January 10, 2012 to February 10, 2012 | Arsenic1005 | Monitoring Or Reporting | Resolved | February 10, 2012 |
| January 1, 2012 to February 10, 2012 | Nitrate1040 | Monitoring Or Reporting | Resolved | February 10, 2012 |
| January 1, 2011 to Not available | Lead and Copper Rule5000 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 2008 to Not available | Radium-2264020 | Monitoring Or Reporting | Resolved | Not available |
| January 1, 1989 to Not available | Selenium1045 | Monitoring Or Reporting | Archived | Not available |
| January 1, 1989 to Not available | Chromium1020 | Monitoring Or Reporting | Archived | Not available |
| January 1, 1989 to Not available | Mercury1035 | Monitoring Or Reporting | Archived | Not available |
| January 1, 1989 to Not available | Nitrate-Nitrite1038 | Monitoring Or Reporting | Archived | Not available |
| January 1, 1989 to Not available | Barium1010 | Monitoring Or Reporting | Archived | Not available |
| January 1, 1989 to Not available | Cadmium1015 | Monitoring Or Reporting | Archived | Not available |
| January 1, 1989 to Not available | Arsenic1005 | Monitoring Or Reporting | Archived | Not available |
Where can I confirm this?
Provider phone: 801-229-7530
How fresh are the sources?
Compare reported values, limits, and sampling periods.
Confirm the matchUse an address, then confirm with your bill or utility.
Keep learningUnderstand testing, treatment, and the limits of public records.